If your Ideal boiler has stopped working and the display is flashing an F and then a 1, the system has lost water pressure. It is one of the most common calls we take in Hull over the winter, and in most cases it is something you can sort out yourself in about ten minutes.
At a Glance
Hull, East Riding | Ideal boilers | F1 means low water pressure | Ideal say top up to between 1 and 1.5 bar
What the F1 code actually means
Ideal’s own fault code guide lists a flashing F and 1 as low pressure, and says the water pressure is too low in the system and will require topping up to between 1 and 1.5 bar.
Your boiler is a sealed system. It holds a fixed amount of water that goes round and round, and it needs a certain amount of pressure behind it to push that water through the radiators. When the pressure drops too far, the boiler shuts itself down rather than running dry. That is the F1.
It does not mean the boiler is broken. It means the system has lost water, and the question worth asking is where it went.
What pressure should an Ideal boiler be at?
Between 1 and 1.5 bar when the system is cold. That is Ideal’s own figure, on both their fault code page and their Logic Combi guide.
Check the gauge when the heating has been off for a while. Pressure rises as the water heats up, so a reading taken mid-cycle will look higher than the boiler’s resting pressure and can send you chasing a problem that is not there.
One thing worth knowing: Ideal’s Logic guide also mentions an original installation pressure of 1 to 2 bar when talking about spotting a leak. If your boiler has a sticker or a mark on the gauge showing a different target, go with what is on your boiler.
How to top up an Ideal boiler
Ideal say the process is the same across the Logic Combi range whether yours is 24, 30 or 35kW.
1. Turn the boiler off
Switch it off at the front panel and let it cool. Topping up a hot system gives you a false reading.
2. Find the filling loop
Usually underneath the boiler. Either a braided silver hose between two small valves, or a built in tap or lever on the underside.
3. Open slowly
Open both valves a little, or turn the tap gently. You will hear water moving. Watch the gauge, not the clock.
4. Stop at 1.5 bar
Close both valves fully. Reset the boiler and the F1 should clear.
If you overshoot: bleed a small amount of water out of a radiator until the gauge comes back down into range. Do not leave it sitting high, because the pressure relief valve will start dumping water outside and you will be back where you started.
L1 and L3: the other Ideal codes that mention pressure
Ideal list two more codes that send you to the pressure gauge, and they catch people out because the fix is not the same.
- L1 asks you to check the water pressure is at 1 to 1.5 bar, the same as F1.
- L3 asks you to turn the boiler off and bleed the air out of your radiators first, and then check the pressure again. Air in the system is the thing to deal with here, not just the gauge reading.
So if you are seeing L3 rather than F1, bleed the radiators before you reach for the filling loop.
If the pressure keeps dropping
Topping up once in a while is normal. Topping up every few weeks is not, and it means water is escaping somewhere. Ideal’s own advice is that if the pressure is still dropping, get in touch with a Gas Safe registered engineer.
The usual culprits are a pinhole leak in pipework under the floor, a pressure relief valve that has stuck part open and is dripping outside, or an expansion vessel that has lost its charge. None of those are fixed by topping up, and the last two need an engineer.
Worth a look before you call: the small copper pipe that comes out through an outside wall near the boiler. If it is wet or dripping, that is your pressure relief valve and that is where your water is going.
Ideal Boiler Still Showing F1?
If you have topped it up and it has come straight back, or you cannot find the filling loop, give us a shout. We cover Hull and the East Riding and we are Ideal Max Accredited Installers.