If your Vaillant has shut down and the display is showing F.22, the system has run low on water. Vaillant describe the fault as no or insufficient water in the product, or the water pressure being too low. It is a common one in Hull homes in the autumn, when the heating goes back on after a summer off.
At a Glance
Hull, East Riding | Vaillant ecoTEC | F.22 means low water pressure | Vaillant’s cold range is 1.0 to 2.0 bar
What F.22 means on a Vaillant
Your heating is a sealed system holding a set amount of water. The boiler needs pressure behind that water to move it round the radiators, and it monitors the level constantly. When it drops too far the boiler shuts itself off rather than firing with not enough water in it, and it tells you why with F.22.
It is a protective shutdown, not a breakdown. The boiler has done exactly what it should.
Vaillant’s pressure figures are not the same as other brands
This catches people out, including some advice you will find online. Vaillant’s own ecoTEC pro operating instructions state that the filling pressure when the heating installation is cold must be between 1.0 bar and 2.0 bar.
That is a wider range than Worcester or Ideal use, so do not top a Vaillant up to a figure you read on a guide written for a different make.
- Below roughly 0.8 bar, the display starts prompting you to fill the system.
- Below 0.5 bar, the boiler switches off and shows F.22.
- Vaillant also note that a house spanning several storeys may need a higher pressure, and to ask a competent person what yours should be.
Read the gauge cold. Pressure climbs as the water heats, so a reading taken while the heating is running will always look better than the truth.
How to top up a Vaillant, the way Vaillant describe it
Vaillant’s operating instructions give owners these steps. Their first instruction is to ask a competent person where your filling cock is, because the arrangement varies between installations and they do not assume you know.
1. Open the radiators
Open all the radiator valves in the system, thermostatic ones included.
2. Open the water supply
Open the heating water supply to the filling tap.
3. Fill slowly
Turn the filling cock on slowly and let water in until the pressure reaches the right level. Then close the supply.
4. Purge and check
Bleed the radiators, check the pressure on the display, top up again if needed, then close the filling cock.
On most Vaillant combis the filling point sits underneath the boiler. Depending on the installation it is either a braided hose between two valves, a built in tap, or a small key that slots into the underside. If you cannot identify yours with confidence, that is the point to stop and ring someone rather than start turning things.
Worth being straight about: Vaillant’s own help page on F.22 says the fault should be left to an expert, while their operating manual gives owners the filling steps above. Both things are true. Topping up is a reasonable job for a confident homeowner who can find their filling point. Anything beyond that, including a boiler that will not hold its pressure, is theirs to look at rather than yours.
If F.22 comes straight back
A system that needs topping up once or twice a year is behaving normally. One that needs it monthly has a leak, and topping it up is treating the symptom.
The things we find most often are a pinhole in pipework under a floor, a pressure relief valve that has stuck slightly open and is quietly discharging outside, or an expansion vessel that has lost its charge. The vessel is the sneaky one, because the pressure looks fine cold and then shoots up when the heating runs.
Before you call, have a look at the small copper pipe poking through an outside wall near the boiler. If it is dripping, you have found where your water is going.
Vaillant Showing F.22 Again?
If it keeps coming back, or you would rather not go hunting for the filling point yourself, we will come and look. Gas Safe registered, covering Hull and the East Riding.